Viability of datacenter cooling systems for energy efficiency in temperate or subtropical regions: Case study

[Display omitted] ►We use the datacenter power efficiency metrics for analyzing the economizer systems. ►We evaluate the air-side economizer and water-side economizer system. ►Results show that outdoor conditions influence facility energy consumption. ►Power Usage Effectiveness (PUE) was computed wi...

Full description

Saved in:
Bibliographic Details
Published in:Energy and buildings 2012-12, Vol.55, p.189-197
Main Authors: Cho, Jinkyun, Lim, Taesub, Kim, Byungseon Sean
Format: Article
Language:English
Subjects:
Citations: Items that this one cites
Items that cite this one
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:[Display omitted] ►We use the datacenter power efficiency metrics for analyzing the economizer systems. ►We evaluate the air-side economizer and water-side economizer system. ►Results show that outdoor conditions influence facility energy consumption. ►Power Usage Effectiveness (PUE) was computed with energy simulation. In general, a proper balance of temperature and humidity control is essential for efficient datacenter operation and is integral to protecting the significant investment in computer and network technology in datacenter facilities. However, the rising costs of energy and the drive to be green are resulting in a greater demand to conserve energy. One method of reducing facility costs for a chilled water plant is by adding an economizer. The purpose of this study is to develop energy models of the most common economizer systems. A normal chiller plant with an air-side economizer and a water-side economizer are compared. Results show that outdoor conditions influence facility energy consumption. This paper provides terminology and definitions for the two different types of economizer modes and compares their energy performance against key datacenter attributes in temperate or subtropical regions. The electrical end use breakdown and the Power Usage Effectiveness (PUE) value for a typical year were estimated. The water-side economizer made it possible to achieve a maximum energy performance improvement of about 16.6% over the reference base cooling system, whereas the air-side economizer made it possible to achieve about 42.4% improvement.
ISSN:0378-7788
DOI:10.1016/j.enbuild.2012.08.012