Loading…

An efficient approach for tracking transients generated by utility shunt capacitor switching

This paper presents an efficient approach for tracking the location of the electric utility shunt capacitor bank that generates switching transients by a limited number of power quality (PQ) meters. The approach is based on measuring the voltage-disturbance energy variations at the meter buses and p...

Full description

Saved in:
Bibliographic Details
Published in:IEEE transactions on power delivery 2006-01, Vol.21 (1), p.510-512, Article 510
Main Authors: Chang, G.W., Shih, M.H., Chu, S.Y., Thallam, R.
Format: Article
Language:English
Subjects:
Citations: Items that this one cites
Items that cite this one
Online Access:Get full text
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:This paper presents an efficient approach for tracking the location of the electric utility shunt capacitor bank that generates switching transients by a limited number of power quality (PQ) meters. The approach is based on measuring the voltage-disturbance energy variations at the meter buses and phase angle changes at the connected branch current due to the reactive power supplied by the switched-on utility capacitor. Both measured energy and phase angle variations are used to identify the location of the switched capacitor through a rule-based tracking algorithm. The proposed method is then tested with the IEEE 30-bus transmission system to show its usefulness.
ISSN:0885-8977
1937-4208
DOI:10.1109/TPWRD.2005.860284